Gyakran Ismételt Kérdések

A UPS reports overload, but the connected load is below its maximum

Utolsó módosítás 5 évvel ezelőtt
There several possibilities to investigate.

Eventhough the apparent power (given in Volt-Amperes) of your loads is smaller than UPS's maximum, due to small Power Factor, the real power (given in Watts) is exceeding the limit:
https://support.powerwalker.com/kb/faq.php?id=5

Your load might have Active Power Factory Correction, while UPS does not support it. APFC causes short peak above its nominal maximum:
https://support.powerwalker.com/kb/faq.php?id=65
https://support.powerwalker.com/kb/faq.php?id=2

Your load has a reactive character (i.e. based on motor or transformer) and creates in-rush currents (peak load) above its nominal maximum:
https://support.powerwalker.com/kb/faq.php?id=58

Kérem várjon!

Kérem várjon.. egy pillanat és kész!